Who this is for
Roofers and GCs
You need the array off the roof on a date, and back on when the roof is done, without owning the electrical liability in between. We coordinate to your schedule and handle the solar side end to end.
Property owners
A roof leak, a re-roof, or storm damage under an existing system. We work with your roofer, your insurer, and your original installer's documentation to get it done once.
O&M providers and asset owners
Module swaps under warranty, racking repairs, and partial removals for HVAC, skylight, or structural work on commercial roofs.
How it works
- Site review. System size, module and racking type, inverter and monitoring, roof type, access, and the roofer's schedule. We confirm what the original installer left behind — drawings, string map, permit set — and fill the gaps if they didn't.
- Baseline. Production snapshot from monitoring and a string-level check (Voc / Isc) before anything is touched, so we can prove the system came back the way it left.
- Safe shutdown and removal. Lockout, rapid-shutdown and inverter isolation, then modules, optimizers or microinverters, and racking removed and labeled by position. Nothing goes back in a different place than it came from.
- Storage. Modules stacked on edge, protected, and kept on site or moved to secure storage — your call. Serials inventoried against the string map.
- Roof work. Your roofer does their job. We coordinate penetrations, flashing, and standoff locations so the racking goes back onto a watertight roof.
- Reinstall. Racking re-set and torqued, modules back in their original positions, wiring and grounding re-terminated, labels restored.
- Verification. String checks against the baseline, insulation resistance, inverter restart, and monitoring confirmed live. A short closeout report with before/after numbers and photos.
What we check on the way back
- Every string's Voc and Isc against the pre-removal baseline
- Insulation resistance on DC strings before reconnection
- Racking torque, flashing, and attachment points at the roof
- Grounding and bonding continuity
- Rapid-shutdown function and inverter commissioning
- Monitoring reporting on every optimizer / microinverter, where fitted
If something was already wrong before we arrived — a bad connector, a cracked module, a dead optimizer — we document it, tell you, and quote the fix separately rather than quietly reinstalling a problem.
Questions we get
- How long does it take?
- Depends on size and access. A typical residential array is a day off and a day on; commercial roofs are quoted per job after the site review. We'll give you a number, not a range.
- Will this void my panel or inverter warranty?
- No, provided it's done to the manufacturer's installation requirements — which is the whole point of having it done by a solar crew rather than the roofer. We document the work so you have the record.
- Do you handle the permit or the utility?
- Most R&R jobs don't need a new permit or interconnection change, but some jurisdictions and utilities want notice. We'll tell you up front what applies to your site.
- Can you find damage while the panels are down?
- Yes — removal is the ideal time for a module-level thermography and electrical check, since every module is accessible. Ask for it when you call.